VTS type single-pole voltage transformers manufactured by KBP Intra Sro (Czech Republic) meet the highest quality requirements.
These voltage transformers has been designed for indoor use on medium voltage networks. The dimensions of the device comply with relevant DIN 42600-8 standard specifications. The cast-resin insulation of voltage transformer is an epoxy mix which is an electric insulant featuring extremely good mechanical properties. The voltage transformers are available with one, two or three secondary windings. The secondary windings are led out to a terminal board. The secondary terminal board has a lockable plastic cover. Secondary cable entry to the secondary terminals is possible through 1 pc of Pg16 packing gland.
The voltage transformer has a galvanized metallic structure resistant to corrosion. Its connector normally designed for earthing is equipped with a durable marking in accordance with relevant specifications.
The device is constructed in such a way that its structure cannot be dismantled and its nameplate cannot be replaced without damaging the calibration mark. The voltage transformer withstands thermal and dynamic impacts caused by an external short-circuit for a period set out in relevant standard.
All components, materials and parts used during the manufacturing process comply with all relevant standards being currently effective and with the generally recognized technical rules. The product does not contain any material containing PCB or asbestos, halogenated hydrocarbons and any other hazardous material to be mandatorily furnished with a descriptive symbol. The voltage transformer is type tested according to EN 61869-1 and EN 61869-3 standards.
Voltage transformers used for metering for accounting are calibrated by MKEH (Hungarian Trade Licensing Office), Authority of Metrology.
Downloadable catalog:
Main technical specifications
Maximum voltage: | 12/17.5 kV, 24/25kV, 36/38,5kV |
Power frequency withstand test voltage: | 28/38 kV, 50kV, 70/80kV |
Impulse withstand test voltage: | 75/95 kV, 125kV, 170/180 kV |
Nominal primary current: | 3000/√3 – 40500/√3 V |
Nominal secondary current: | 100/√3, 110/√3, 120/√3 V |
Accuracy class – measuring core: | 0.2, 0.5, 1 |
Accuracy class – protection core: | 3P, 6P |
Accuracy limit factor – protection core: | 5, 10, 15, 20, 25, 30 |
Power: | 5,7, 5, 10, 15, 20, 30, 50, 75, 100, 150 VА |
Number of cores with calibration capability: | 3 (for versions 12/17.5 kV, 24/25kV only) |
Maximum power: | 400 VA |
Frequency: | 50 Hz |
Insulation temperature class: | E |
Operating temperature: | -5 to + 40 °C |
Storage temperature: | -50°C to +60°C |
Standards: | EN 60044-2, EN 61869-1, EN 61869-3, GOST 15 150 |